The ROTRONIC humidity, temperature, dew point
transmitters and probes feature reliable, accurate measurement
and the ability to calibrate on-site. Designed for fixed
installation, these precision instruments are used for humidity,
temperature or dew point measurement in applications ranging
from the control of a simple office building to specialized
applications such as a computer room, clean room, pharmaceutical
research room, stabilization room or storage area,
semi-conductor fabrication area, or the control of a
manufacturing process.
|
|
Commercial HVAC: Building Automation, Energy Management Systems |
HF3 series
 |
► Integral probe (cannot be separated)
► Limits at probe: 0...100%RH and -40...60°C / -40...140°F
► Accuracy: ± 2 %RH and 0.3ºC / 0.5ºF
- One or two analog output signals (current or voltage)
corresponding to relative humidity, temperature, dew or frost
point
- Duct, wall and space mount configurations
- NEMA 4 / IP6 enclosure (depends on model)
- 2-wire, loop-powered and 3-wire models
- On-site calibration / adjustment with the HP23 handheld
calibrator
- User configurable
|
|
Precision HVAC: Computer Rooms, Clean Rooms, Research Labs,
Semi-conductor Fab Areas |
|
HF4 series
 |
► Integral probe (cannot be separated)
► Limits at probe: 0...100%RH and -50...100°C / -58...212°F
► Accuracy: ± 1.0%RH and 0.2ºC / 0.4ºF
- One or two analog output signals (current or voltage)
corresponding to relative humidity, temperature, dew or frost
point
- Digital interface option instead of analog output signals
- Duct and wall mount configurations
- MEMA 4 / IP65 enclosure
- 2-wire, loop-powered and 3-wire models
- On-site calibration / adjustment with the HP23 handheld
calibrator
- User configurable
|
|
Research Laboratories, Manufacturing and Storage of
Pharmaceuticals, Process Control |
|
HF5 series

 |
► Large choice of interchangeable, plug-in probes
► Limits at probe: 0...100%RH and -100 to 200°C (-148 to 392°F)
► Accuracy: ± 0.8%RH and 0.1ºC / 0.2ºF
- One or two analog output signals (current or voltage)
corresponding to relative humidity, temperature, dew or frost
point, or other calculated parameter such as enthalpy, mixing
ratio, etc.
- Digital interface option with or without analog output signals
- Probe can be separated from transmitter by up to 100m (330 ft)
cable
- Duct and wall mount configurations
- NEMA 4 / IP65 enclosure
- 2-wire, loop-powered and 3-wire models
- Plug-in probe can be removed for easier maintenance off-site
or on-site
- User configurable
Note: temperature limits depend on probe model
|
|
Industrial Process Control |
|
HF7 series

 |
► Integral probe (cannot be separated)
► Limits at probe: 0...100%RH and -100...200°C / -148...392°F
► Accuracy: ± 1.0%RH and 0.2ºC / 0.4ºF
► Designed for rough environments
- One or two analog output signals (current or voltage)
corresponding to relative humidity, temperature, dew or frost
point
- Duct and wall mount configurations
- Available with a hard-wired probe separated by 2m (6.5 ft)
cable
- 2-wire, loop powered and 3-wire models
- Robust NEMA 4 / IP65 metal enclosure and metal probe body
- On-site calibration / adjustment with the HP23 handheld
calibrator
- User configurable
|
|
HygroFlex series
 |
► Large choice of interchangeable, plug-in probes
► Limits at probe: 0...100%RH and -50...200°C / -58...392°F
► Accuracy: ± 1.0%RH and 0.2ºC / 0.4ºF
- Up to 3 analog output signals (current or voltage)
corresponding to relative humidity, temperature, dew or frost
point, or other calculated parameter such as enthalpy, mixing
ratio, etc.
- Digital interface option with or without analog output signals
- NEMA 4 / IP65 enclosure (optional metal enclosure)
- Probe can be separated from transmitter by up to 200 m / 656
ft cable
- Plug-in probe can be removed for easier maintenance off-site
or on-site
- User configurable
Note: not compatible with AirChip 3000 products |