Home Page | M2 Series Main Page | Contact us

red_button.gif (982 bytes) M2 Series Specifications

PROBE M22 M23
Probe type HygroClip S
Humidity sensor ROTRONIC C94 thin film capacitive
Temperature sensor Pt100 RTD
Operating limits 0...100%RH
-40...85°C / -40...185°F
Repeatability better than 0.5%RH and 0.1°C/°F
Humidity sensor stability better than 1% RH per year
Sensor protection type D15G, stainless steel wire mesh, PPS frame
Probe material Polycarbonate
TRANSMITTER M22 M23
Circuit type 2-wire loop-powered 3-wire
Signal type 4...20 mA 0...20 mA, 4...20 mA
0...1V, 0...5V, 0...10V
(user selectable)
Measuring range 0...100% RH
0...100°F (other ranges are available)
System accuracy at 23°C ± 1.5% RH / ± 0.3°C (± 0.5°F)
Operating limits 0...99% RH non condensing
-40...60°C (-40...140°F)
-30...60°C (-22...140°F) with optional display
Power supply 10...28 VDC, 10 + 0.02 x load
2 x 20 mA
15...35 VDC (65 mA) or 12...24 VAC
Maximum load for current outputs 250 Ohm
Minimum load for voltage outputs n/a 1000 Ohm
User configurable output signals n/a output scale and temperature unit configurable with the HW3 software

output signal type (current or voltage) configurable with solder pads
Display option No Yes
LC, 2 line numeric
1 line alphanumeric
1/4 character height, resolution 0.1
Electrical connections Cable grip and terminals
Housing material ABS
Protection grade IP65/NEMA4
Housing dimensions w/o probe 154 x 72.5 x 48 mm (6.06 x 2.86 x 1.89")
Weight 300 g / 0.7 lb