Home Page | M3 Series Main Page | Contact us
M3 Series Specifications
PROBE Probe type HygroClip S Humidity sensor ROTRONIC C94 thin film capacitive Temperature sensor Pt100 RTD Operating limits 0...100%RH
-40...85°C / -40...185°FRepeatability better than 0.5%RH and 0.1°C/°F Humidity sensor stability better than 1% RH per year Sensor protection type D15G, stainless steel wire mesh, PPS frame Probe material Polycarbonate TRANSMITTER Circuit type 3-wire Signal type 0...20 mA, 4...20 mA, 0...1V, 0...5V, 0...10V
(user selectable)Analog outputs Two analog outputs corresponding to any combination of the following:
relative humidity, temperature, computed parameter (dew point, etc.)
or user defined calculationDigital output / Networking RS485 - up to 31 M3 transmitters on one network connected as slaves to one HygroFlex 2 or 3 master. RS232 connection from master to PC. Computed parameter dew point, wet bulb, enthalpy, vapor concentration, specific humidity, mixing ratio, vapor concentration at saturation, partial pressure of water vapor, saturation pressure of water vapor, or a user defined calculation such as the difference between temperature and dew point Measuring range 0...100% RH, 0...100°F
other ranges are available for humidity, temperature
and the computed parameterSystem accuracy at 23°C ± 1.5% RH / ± 0.3°C (± 0.5°F) Operating limits 0...99% RH non condensing
-40...60°C (-40...140°F)
-30...60°C (-22...140°F) with optional displayPower supply 15...35 VDC (65 mA) or 12...24 VAC Maximum load for current outputs 250 Ohm Minimum load for voltage outputs 1000 Ohm User configurable analog outputs scale and unit of each analog output configurable with the HW3 software
output signal type (current or voltage) configurable with solder padsDisplay option LC, 2 line numeric
1 line alphanumeric
1/4 character height, resolution 0.1Electrical connections Cable grip and terminals Housing material ABS Protection grade IP65/NEMA4 Housing dimensions w/o probe 154 x 72.5 x 48 mm (6.06 x 2.86 x 1.89") Weight 300 g / 0.7 lb