Home Page | Roline L Series Main Page | Contact us
Roline L Series Specifications
PROBE L12 L13 Humidity sensor ROTRONIC Hygromer ™ C94 thin film capacitive Temperature sensor Pt100 RTD Operating limits 0...100%RH
-40...60°C / -40...140°FRepeatability better than 0.5%RH and 0.1°C/°F Humidity sensor stability better than 1% RH per year Sensor protection L12D / L13D: PVC foam filter
L12S / L13S: n/aProbe material L12D / L13D: Polycarbonate
L12S / L13S: n/aTRANSMITTER L12 L13 Circuit type 2-wire loop-powered 3-wire Signal type 4...20 mA 0...20 mA, 4...20 mA
0...1V, 0...5V, 0...10VStandard output ranges 0...100% RH
0...50°C or 0...100°FAccuracy at 23°C ± 3.0% RH / ± 0.5°C (± 0.9°F) Operating limits 0...99% RH non condensing
-40...60°C (-40...140°F)Power supply 10...28 VDC, 10 + 0.02 x load
2 x 20 mA10...35 VDC (50 mA) or 12...24 VAC
minimum 15 V for current outputs
< 50 mAMaximum load for current outputs 250 Ohm Minimum load for voltage outputs n/a 1000 Ohm Electrical connections L12D / L13D: cable grip and terminals
L12S / L13S: terminalsHousing material ABS Protection grade L12D / L13D: IP65/NEMA4
L12S / L13S: IP52 / NEMA5Weight L12D / L13D: 119 g / 4.2 oz
L12S / L13S: 94 g / 3.3 oz